Temperature and humidity converter with relay outputs, Ethernet interface, and discrete inputs. External probes can be connected. Designed for installation in a 19” 1U rack. — H3531R
Available on request
Delivery across Russia
Order phone: +7(800)777-18-50
Description
The converter is equipped with two relay outputs for signaling, indication, or control of external devices. It also has three discrete inputs for connecting external devices such as smoke detectors, motion sensors, etc. Delay settings, hysteresis, and sound signal are enabled for each relay. It is installed in a 19” 1U rack. Parameters are easily configured using a computer or the keyboard on the sensor's front panel. The converter is controlled by a microprocessor housed in a durable plastic case with terminal connectors. A large two-line LCD display is designed to simultaneously show two parameters. The display can be turned off if necessary.
Recently, temperature and humidity levels have been considered as the most important parameters responsible for indoor climate quality. Especially in buildings and rooms with large gatherings of people, such as conference halls, hospitals, schools, cinemas, theaters, and wellness centers.
With the help of such sensors, engineers, environmental experts, and healthcare specialists can optimize ventilation to create a comfortable and "Healthy" indoor climate.
ATTENTION, the device is currently discontinued.
- Specifications
- Overall Drawing
- Electrical diagram
- Applications
|
Sensor |
H3531R |
|
|
Output signal |
2x Relay + Ethernet |
|
|
Temperature |
Range |
-30 to +105°C |
|
Accuracy |
±0.4°C |
|
|
Relative Humidity (at RH 5-95% and at 23°C) |
Range |
0 to 100 %RH |
|
Accuracy |
±2.5 %RH |
|
|
Discrete inputs |
yes |
|
|
Sensor power supply voltage |
9 - 30 Vdc |
|
|
Maximum switchable voltage, current and power by relay output |
50V, 2A, 60VA |
|
|
Accuracy and range of dew point temperature measurement |
±1.5°C at ambient temp. T<25°C and RH >30% |
|
|
Accuracy and range of absolute humidity measurement |
±1.5 g/m3 at ambient temp. <250C, range 0 to 400 g/m3 |
|
|
Accuracy and range of specific humidity measurement |
±2.1 g/kg at ambient temp. T < 35°C |
|
|
Accuracy and range of specific enthalpy measurement |
±3 kJ/kg at ambient temp. T < 25°C |
|
|
Accuracy and range of mixture component ratio measurement |
±2 g/kg at ambient temp. T < 35°C |
|
|
Sensor / external sensor protection class |
IP30 |
|
|
Sensor operating temperature range |
From -30 to +80°C |
|
|
External sensor operating temperature range |
From -30 to +105°C |
|
|
Operating humidity range (without condensation) |
0 to 100 %RH |
|
|
Storage temperature range |
From -30 to +80°C |
|
|
Recommended calibration interval |
1 year |
|
|
Dimensions / Weight |
483 x 44 x 45 mm (W x H x D), one 19" rack unit 1U / 1090 g |
|
|
Warranty |
3 years |
|

Connection diagram with power adapter

Connection diagram with power supply via Ethernet cable using PoE splitter



Connecting relay to sensor outputs