Explosion-proof level transmitter — 26Y Ei

Available on request
Delivery across Russia
Order phone: +7(800)777-18-50

0 RUB

Description

These level transmitters are approved for use in hazardous areas of group II (gas and dust). Possible hazardous zones for the use of pressure transmitters, categories and groups of explosive mixtures of gases and vapors with air – in accordance with the requirements of the Customs Union Technical Regulation TR CU 012/2011 "On the safety of equipment for operation in explosive atmospheres". Explosion protection marking: 0ExiaIICT4/T5/T6.

Transmitters of the Y series have a very small temperature error. This is achieved by using an additional circuit that includes a temperature sensor, which divides the temperature range into sections 1.5K wide. The values of zero temperature coefficient (TC) and compensation TC are calculated for each section and embedded in the additional circuit. During the operation of the transmitter, these values are included in the analog signal depending on the temperature. Each temperature value is a "calibration temperature" for this transmitter. Accuracy is mainly determined by linearity. The possible temperature range of 180K is represented by 120 sections. The wider the temperature range, the greater the number of tests required to minimize the error of this mathematical model.

  • Specifications
  • Connection diagram
  • Applications

Specification

Value

Pressure range*

from 0…1 mH2O to 0…200 mH2O

Output signal

4…20 mA / 0…10 V / 0.5…4.5 V / 0…5 V

Basic error

0.25% FSO

Operating temperature

-20…100°C

Housing material

stainless steel 316L

Cable material

PE polyethylene

Sensor diameter

20 mm

Overloads

x2 measurement range

Bandwidth

2 kHz

Explosion protection class

EX ia

* - any special ranges are available, for example: 0…12 mH2O

 

 

Total error at 0…50°C

Measurement ranges, FSO

Basic error

Typical

Max.

> 2…10 bar

±0.25 %FSO

±0.3% FSO

±0.5 %FSO

> 0.3…2 bar

±0.25 %FSO

±0.6 %FSO

±1.0 %FSO

0.1…0.3 bar

±0.5 %FSO

±2 mbar

±3 mbar

Cable color 2-wire
4…20 mA 
3-wire
Voltage 
white   GND
red OUT/GND +OUT
black +Vcc +Vcc

 

Type

2-wire

3-wire

3-wire

Output signal

4…20 mA

0…10 V

0…5 V

Output signal range

3.2…22.3 mA

-1.2…11.2 V

-0.6…5.6 V

Power supply

10…30 VDC

15…30 VDC

10…30 VDC

Load resistance

< (U-10 V) / 0.025 A

> 100 kΩ

> 100 kΩ

Maximum frequency

2 kHz

2 kHz

2 kHz

Power consumption

 

max. 5 mA

max. 5 mA

Send request