High-precision piezoresistive level sensor — 26X
Available on request
Delivery across Russia
Order phone: +7(800)777-18-50
Description
The general industrial level sensor series 26X is the perfect solution for those who want to achieve high quality and measurement accuracy at a competitive price.
In high-precision level sensors of the 26X series, temperature dependence and non-linearity are precisely compensated in the microcontroller using a mathematical model. In addition to the RS485 interface, measurement results can also be output via the built-in digital-to-analog converter as a configurable analog signal. Enhanced lightning protection is also available as a option.
Features
- RS485 interface possible together with analog interface
- Analog interface can be reconfigured or disabled via the RS485 interface
- Modbus RTU protocol for measurement configuration and adjustment
- Excellent long-term stability
- Operation without maintenance for many years
Technical Solutions
- Piezo-resistive pressure sensor isolated from the medium
- Robust stainless steel housing with high-quality cable gland
- High-quality pressure transducer and proven mathematical compensation
Standard Applications
- Measurement of hydrostatic pressure
- Level measurement: groundwater, surface water bodies
- Fill level measurement: water tanks, fuel tanks
- Specifications
- Overall dimensions drawing
- Applications
Specifications |
||
| Pressure | ||
| Accuracy at room temperature (20…25 °C) | ≤ ± 0.1% FSO | Linearity (best fit straight line), pressure hysteresis, repeatability, zero offset, gain factor |
| Total error (0…50 °C) | ≤ ± 0.25% FSO | Maximum deviation within compensated pressure and temperature range. Experience shows that outside the compensated temperature range, total error within ambient temperature range increases by 0.1% FSO. |
| Compensated temperature range | 0…50°C | Option: Other additional temperature ranges possible within -20…85°C |
| Long-term stability | ≤ ± 0.15% FSO | Per year under standard conditions |
| Position dependence | ≤ ± 1.5 mbar | Calibrated in vertical mounting position with threaded connection facing downwards |
| Resolution | 0.002% FSO | Digital |
| Signal stability | 0.01% FSO | Digital noise-free |
| Internal measurement frequency | ≥ 1800 Hz | For version «3-wire + digital (0…10 V, 0…5 V)» > 6000 Hz |
| Pressure range margin | ± 10% | Outside the pressure range margin, +Inf / -Inf is displayed. In case of device error, NaN is displayed. |
| Note | For pressure ranges < 1 bar, all data apply to the full scale output (FSO) signal of 1 bar. | |
| Temperature | ||
| Accuracy | ≤ ± 1.5°C | Temperature is measured on the pressure sensor (silicon chip) located behind the metal separating membrane. Values are valid within the compensated temperature range. |
| Resolution | ≤ 0.01°C | |
| Internal measurement frequency | > 10 Hz | |
.jpg)