Economical and reliable flow meter for ventilation — SS 20.100
Available on request
Delivery across Russia
Order phone: +7(800)777-18-50
Description
SS 20.100 is a high-quality and affordable flow and temperature sensor for air and gases. The sensor is housed in a compact and convenient case and features a universal sensitive element that measures airflow in any direction. This eliminates the need to align the sensor with the flow.
The sensor comes with a mounting bracket that allows for easy and quick installation of the device in two different ways. Thanks to the extension mounting tubes, it is possible to adjust the maximum immersion depth of the sensor, which also allows its use on pipelines with large diameters.
The sensitive element is fully enclosed in a metal housing, making the flow meter resistant to dust ingress. Additionally, in case of contamination, the sensitive element can be easily and quickly cleaned without fear of damaging the device.
All these advantages make the SS 20.100 suitable not only for HVAC (heating, ventilation, air conditioning) applications but also for clean rooms, for example, for precise air control in fume hoods.
Advantages
- Easy installation, no need for flow alignment, adjustable immersion depth, probe length extension;
- All electronic components are built into the device probe;
- LED status indication;
- Durable and stable – maintenance-free;
- Easy to clean (dust resistant).
- Specifications
- Overall Drawing
- Applications
| Characteristic | Value |
| Measured parameters | air velocity wN, normalized to standard conditions (20 °C and 1013.25 hPa) Medium temperature TM |
| Measured medium | air and gases |
| Measurement range wN Measurement accuracy1) wN |
0 ... 2.5 m/s ± (4 % of reading + 0.05 m/s) 0 ... 10 m/s ± (4 % of reading + 0.2 m/s) 0 ... 20 m/s ± (4 % of reading + 0.4 m/s) |
| Minimum activation threshold wN | 0.2 m/s |
| Reproducibility wN | ± 1.5 % of reading |
| Measurement range TM | 0…+60 °C |
| Measurement accuracy TM (wN > 2 m/s) | ± 1 K (10 … 30 °C); ± 2 K in other ranges |
| Response time (t90) wN | about 10 s (step from 0 to 5 m/s) |
| Operating temperature | -10…+60 °C |
| Operating humidity | 0...95 % relative humidity (RH), no condensation |
| Operating pressure | atmospheric (700 ... 1,300 hPa) |
| Supply voltage UB | 24 V DC ± 20 % |
| Current consumption | typ. < 35 mA (max. 80 mA) |
| Analog outputs | 0 … 10 V |
| Power load | RL ≥ 10 kOhm; CL ≤ 1 nF |
| Electrical connection | non-detachable cable, open ends, length 2 m, 4-pin, 0.25 mm², PVC |
| Cable length (recommended) | max. 15 m |
| Protection class | IP 40 |
| Electrical safety class | III (SELV) |
| Min. immersion depth | 35 mm |
| Dimensions | ø 12 mm, probe length 144 mm |
| Material | Polycarbonate, ABS plastic, nickel-plated brass |
| Weight | 50 g (probe) |
| Delivery set | probe, mounting bracket, extension tube, user manual |
1) Under reference conditions

Installation elbow: