Ammonia Detector-Transmitter — E2611-NH3

Available on request
Delivery across Russia
Order phone: +7(800)777-18-50

0 RUB

Description

The ammonia detector E2611-NH3 is a representative of the new line of multifunctional measuring instruments PluraSens®.

The detector can be used in agriculture (in livestock and poultry facilities), in industrial refrigeration units, and other premises where dangerous concentrations of ammonia may be reached.

By default, the alarm triggers at 25 and 35 ppm of ammonia. The user can also set other threshold concentration values.

Thanks to two relays with a changeover contact, the detector can be used for remote notification and control. When threshold concentrations are reached, an audible signal also activates.

The detector is equipped with a fully calibrated latest-generation metal oxide sensor with temperature and humidity compensation, ensuring high stability and reliability of readings, as well as a long service life of the device.

To connect the detector to ventilation, security, and building automation systems, two configurable analog outputs and an RS485 interface operating with the Modbus RTU protocol can be used.

Key Features

  • Durable metal oxide sensor
  • Detection range 0...1000 ppm NH3
  • Resolution 1 ppm NH3
  • Alarm trigger thresholds 25/35 ppm

WARNING, the device is currently discontinued.

  • Specifications
  • Connection
  • Overall dimensions drawing
  • Applications
Specifications
Calibration ammonia NH3
Sensor type durable metal oxide sensor
Sampling method diffusion
Detection range 0...1000 ppm NH3
Resolution 1 ppm NH3
Accuracy ± 5 ppm NH3
Sensor lifespan > 5 years
Power supply 11...30 V DC or 90...265 V AC
Digital interface RS485, Modbus RTU protocol
Alarm 85 dB sound signal
Analog outputs 2 × 4-20 mA / 0-10 V, configurable
Output relays 2 single-pole relays (normally open contact),
  250 V AC / 30 V DC, up to 5 A
Default alarm trigger threshold  25 / 35 ppm
Housing ABS plastic with ventilation slots,
  wall mounting, protection class IP20
Dimensions H85 × W85 × D37 mm
Operating conditions -30...+70 °C, 0...95 %RH, non-condensing

Send request

Request a callback

Information sent successfully

Благодарим за обращение. Ваша заявка будет рассмотрена в течение рабочего дня. Для получения более оперативного ответа, пожалуйста, обращайтесь по телефонам:

+7 (812) 309 56 05 (многоканальный)
+7 (812) 696 00 06
+7 (495) 721 88 93